System installation Western Branch Diesel
Generator Install Facility

Application: Standby Emergency Power WBD Facility

Model Specs: Detroit Diesel 60Kw Standby

Fuel: Diesel 500 gallons slow turn, long term storage

Solution:  Prior to the start of the 2007 hurricane season risk assessment was performed on the standby generator which provides emergency power to several buildings on the WBD facility.  Old tanks, spoiled fuel, and lack of fuel maintenance were primary concerns.  The Algae-X system was installed along with a new tank and piping bringing the system up to code providing peace of mind, security and immediate engine start.

Product: Algae-X STS6000-4GPM.  A fully automated fuel polishing system moving 4 gallons per minute, programmable timer, 80 hour memory (for total power failure), inlet screen/water separator, spin on fine particulate secondary filter, full alarm display and system status on door.  Treatment of fuel with proper proportion of AFC705 Fuel Catalyst.

Notes: Initial startup of the system lasted for 1.5 hours of run time.  The unit shutdown from a no flow alarm.  Inspection showed that the new fuel delivered came with free water.  The inlet water separator removed that and the fine particulate spin on filter absorbed the balance.  Filters were replaced and the system has worked flawless for over 12 months and almost 300 hours.

 

Click On Any Photo To Enlarge

New 500 gallon fuel tank Piping penetrations through wall
New 500 gallon fuel tank Piping penetrations through wall
Fuel filter on generator STS cabinet and fuel piping
Fuel filter on generator Sts6000 cabinet and fuel piping
New fuel drained from filter after 1 hour run time Open cabinet showing component arrangement
NEW Fuel drained from filter after 1 hour run time Open cabinet showing component arrangement

 